DDSU666 (Direct chint meter ) + mbpoll Command Reference Version : 1.0 Prepared For : Field & Deployment Teams Platform : Raspberry Pi / Linux Tool : mbpoll Purpose This document explains how to communicate with the CHINT DDSU666 Direct Smart Meter using Modbus RTU and the mbpoll tool. It covers: • Reading electrical parameters • Setting meter addresses • Verifying communication • Preparing for OpenEMS integration 2. Hardware & Software Requirements Hardware • DDSU666 (Direct Version) • RS485 → USB Converter • Raspberry Pi / Linux PC • Correct RS485 wiring (A(converter)↔24(meter com-port terminal), B(converter)↔25(meter com-port terminal), GND recommended) Software Install mbpoll: sudo apt update sudo apt install mbpoll Check serial port: ls /dev/ttyUSB* Example output: /dev/ttyUSB0 3. Communication Parameters (Confirmed) Parameter Value Protocol Modbus RTU Baud Rate 9600 Data Bits 8 Parity None Stop Bits 2 Format 8N2 Float Order Big Endian Addressing 0-Based These parameters must always be used. 4. Standard mbpoll Format All commands follow this format: mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 -r -c /dev/ttyUSB0 -a -1 Where: •     = Modbus register •     = Number of values •     = Meter address (NO.) 5. Electrical Parameters Summary: Voltage: 0x2000 Current: 0x2002 Active Power: 0x2004 Power Factor: 0x200A Frequency: 0x200E Energy: 0x4000 5.1 Voltage (V) — Register 0x2000 Meter ID = 1 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2000 -c 1 /dev/ttyUSB0 -a 1 -1 Meter ID = 2 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2000 -c 1 /dev/ttyUSB0 -a 2 -1 5.2 Current (A) — Register 0x2002 Meter ID = 1 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2002 -c 1 /dev/ttyUSB0 -a 1 -1 Meter ID = 2 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2002 -c 1 /dev/ttyUSB0 -a 2 -1 5.3 Active Power — Register 0x2004 Meter ID = 1 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2004 -c 1 /dev/ttyUSB0 -a 1 -1 Meter ID = 2 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2004 -c 1 /dev/ttyUSB0 -a 2 -1 5.4 Power Factor — Register 0x200A Meter ID = 1 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x200A -c 1 /dev/ttyUSB0 -a 1 -1 Meter ID = 2 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x200A -c 1 /dev/ttyUSB0 -a 2 -1 5.5 Frequency (Hz) — Register 0x200E Meter ID = 1 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x200E -c 1 /dev/ttyUSB0 -a 1 -1 Meter ID = 2 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x200E -c 1 /dev/ttyUSB0 -a 2 -1 5.6 Energy (kWh) — Register 0x4000 Meter ID = 1 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x4000 -c 1 /dev/ttyUSB0 -a 1 -1 Meter ID = 2 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x4000 -c 1 /dev/ttyUSB0 -a 2 -1 6. Reading Multiple Values Use -c option to read multiple registers. Example ( Voltage + Current Together) mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2000 -c 2 /dev/ttyUSB0 -a 1 -1 7. Meter Address Register: 0x0006 mbpoll -m rtu -b 9600 -P none -s 2 -t 4:int16 -0 \ -r 0x0006 -c 1 /dev/ttyUSB0 -a 2 -1 Example Output: [6]: 2 8. Changing Address Only one meter connected. Power cycle after change. Change Address (2 → 1) mbpoll -m rtu -b 9600 -P none -s 2 -t 4:int16 -0 \ -r 0x0006 /dev/ttyUSB0 -a 2 -W -- 1 Power Cycle Turn OFF → ON the meter. Verify mbpoll -m rtu -b 9600 -P none -s 2 -t 4:int16 -0 \ -r 0x0006 -c 1 /dev/ttyUSB0 -a 1 -1 9. Health Check Voltage should be 220–240V. mbpoll -m rtu -b 9600 -P none -s 2 -t 4:float -B -0 \ -r 0x2000 -c 1 /dev/ttyUSB0 -a 1 -1 10. Common Issues Timeout Errors •    Duplicate IDs •    Wrong wiring •    Wrong stop bits •    Multiple meters during setup Incorrect Float Values Use -B option. Current / Power = 0 Normal when: •    No load •    Bench testing 11. Deployment Workflow For large installations: •    Connect one meter •    Convert to Modbus •    Set address •    Test voltage •    Install •    Repeat •    Never deploy duplicate addresses. Connect → Configure → Test → Install 12. System Status ✔ Modbus Enabled ✔ 9600 8N2 Confirmed ✔ Big-Endian Floats ✔ Multi-meter Bus Working ✔ Ready for OpenEMS