Sezibwa meter replacement log Sezibwa meter replacement log One entry per customer meter swap at Sezibwa (gateway gw-pi2). Record every system that points at a meter serial, because each one must be switched separately: the OpenEMS gateway config, the customer app ( meter_sources ) and the billing engine (MBE device + household link). Customers are identified here by Modbus address and serial only. Summary Date Modbus address Old serial New serial Status 2026-09-14 7 210302003356 200326020197 All systems switched 2026-09-24; closing 244.54 kWh, opening 0.31 kWh 2026-09-14: address 7, 210302003356 to 200326020197 Why it was replaced. The old meter stopped answering on the meters bus on 2026-08-29 at 23:07 UTC (logger issue #82). It was later found physically absent. Its last register value seen on the backend was 229.35 kWh on 2026-09-04. New meter. CHINT DDSU666 serial 200326020197, on Modbus address 7. The first backend data is from 2026-09-14; the register read 16.16 kWh on 2026-09-24. Systems switched: System Change Date Reference OpenEMS gateway (gw-pi2) New meter component meter200326020197 on unit 7 2026-09-14 microgrid-gateway PR #68 Customer app meter_sources row repointed to meter200326020197/ActiveConsumptionEnergy , history start 2026-09-14; daily usage backfilled 14 to 24 Sep with the production backfill script (11 days, sums match the register) 2026-09-24 this page Billing engine (MBE) New device "(new meter)" added on edge sezibwa-rentals-gw-pi2 as a Consumption meter 2026-09-24 this page Billing engine (MBE) Household billing device changed to the new device (Change billing device); old device now unlinked; invoice meter serial field set to 200326020197 by hand 2026-09-24 MBE UI gap reported: serial does not follow a device change Closing and opening readings (from the swap thread, Element product room, 2026-09-14). Old meter 210302003356 read 244.54 kWh just before removal. New meter 200326020197 read 0.31 kWh at installation (about 12:15 EAT), on Modbus address 19. The old meter's register kept counting while it was off the bus, so there is no unmetered gap: its closing reading covers 30 Aug to 14 Sep. September bill. The billing engine takes one meter per household per period, so bill this customer with one manual reading ( manualReadings in the generate call) that joins the two meters: Start End kWh Old meter 223.52 (August end, when it went silent) 244.54 21.02 New meter 0.31 reading at September close end minus 0.31 Manual reading to enter 223.52 244.54 + (new end - 0.31) sum of both Check first that the August bill really ended this customer at 223.52 kWh. Watch. A stray 0.35 kWh value appears on 2026-09-14 under the old channel name. That was the new meter answering on address 7 before its component was renamed, not the old meter.