NFE Daily Brief (gw-pi2, Sezibwa)

NFE daily brief

Written each morning by Claude Haiku from the day's data. Newest first, last 30 days.

2026-10-16

Daily brief: Sezibwa Rentals battery, 16 October 2026 (EAT)

Arbitrage window (18:00–23:59): The battery fell from 91.3% to 15.0% and discharged 7.97 kWh. It reached the 15% floor.

Grid outage: One outage, 03:44 to 05:03 EAT, lasting 79 minutes. The battery started at 98%, dropped to a low of 89%, and ended at 89%. It supplied 0.93 kWh. The day's grid-off total was recorded as 80 minutes.

Evening L3 voltage: 207 minutes below 207 V, with a lowest reading of 199.8 V. This is the known grid-side pattern.

Data quality: All 10 meters reported. None were sparse or silent.

Modbus read errors: 311, against an expected figure of about 260 (about 100 baseline plus about 160 from the nightly 00:00–02:00 charging burst).

Needs attention: Modbus read errors at 311, above the expected ~260. Review the Modbus communication logs for the day.

2026-10-15

Daily brief: Sezibwa Rentals battery, 15 October 2026 (EAT)

Arbitrage window (18:00–23:59): The battery started at 89.0% and ended at 20.3%, discharging 6.94 kWh. The day's lowest state of charge was 20.0%.

Grid outages: None. Grid-off time was 0.0 minutes.

Evening L3 voltage: L3 was below 207 V for 180 minutes, with a lowest reading of 197.6 V. This is the known grid-side sag pattern. L1 and L2 minimums were 220.5 V and 212.3 V.

Modbus errors: The daily count was not available. Normal is about 100 per day.

Meters: All 10 checked meters reported. None were sparse or silent.

Needs attention: nothing

2026-10-14

Daily brief: Sezibwa Rentals, 14 October 2026

Arbitrage window (18:00–23:59): The battery started at 89% and ended at 24%, discharging 6.7 kWh. Its lowest level for the day was 15%.

Grid outages: None. Power was off for 0 minutes.

Evening L3 voltage: The lowest L3 reading was 193.5 V. L3 spent 233 minutes below 207 V. This matches the known grid-side sag pattern.

Modbus errors: 275 for the day. Normal is about 100 plus the nightly burst from midnight to 2 AM, roughly 260 in total, so this is slightly higher than expected.

Needs attention: Modbus read errors were slightly above expected (275 vs. about 260). Check whether this repeats tomorrow.

2026-10-13

Daily brief, Sezibwa Rentals battery, 13 October 2026

The evening arbitrage window ran from 89% to 15% battery charge, discharging 7.5 kWh. The battery held the 15% floor.

There was no grid outage today (0 minutes).

Evening voltage on phase L3 was below 207 V for 189 minutes. The lowest L3 reading was 197.6 V. This matches the known evening pattern.

Modbus read errors totalled 230. That is within the normal range, which allows about 100 per day plus the nightly burst from midnight to 2 AM while the battery charges.

Needs attention: nothing.