Cumulative record of the TOU battery arbitrage on gw-pi2 (Sezibwa). Each night the inverter discharges the battery during a peak-tariff window and recharges it from the grid at the off-peak rate from 00:00. Daily progress goes to the Element business room; this page is the running record. It is rebuilt from the OpenEMS backend by scripts/arbitrage_tracker.py in the nfe-modbus-energy-logger repo.

Settings and why they were chosen: Arbitrage Window and Thresholds (decision record).

Last updated: 2026-10-05 06:12:30 EAT.

Totals

Measure Value
Nights armed 75
Energy shifted to peak 12.9 kWh
Estimated net saving 2,442441 UGX
Average per armed night 1.852.58 kWh, 349488 UGX
Projected per month at that rate 10,46614,648 UGX

Night by night

Night Config Window Start SoC start SoC end Shifted (kWh) Peak (kW) Lowest pack (V) Saving (UGX) Recharge 00-06 (kWh) Notes
2026-09-26 v12 22:00-23:59 22:03 78% 48% 3.08 6.1 50.96 582 5.9 first armed night
2026-09-27 v13 off 0 0 4.5 disarmed: SoC 65% after the 27 Sep overload outage
2026-09-28 v14 21:30-23:30 21:33 87% 64% 2.28 4.6 51.45 432 4.1 window moved to 21:30-23:30
2026-09-29 v15 off 0 0 5.5 disarmed: SoC 61% after the 05:15-07:51 grid outage
2026-09-30 v17 21:00-23:00 21:03 87% 60% 2.75 6.3 50.94 519 4.5 window 21:00-23:00, no more manual disarms
2026-10-01 v17v18 21:00-23:00off 51% 50% 0.000.0 52.50 10 5.7 skipped: two outages left SoC at 51% before the window
2026-10-02 v17v18 21:00-23:00off 87% 86% 0.000.0 53.00 0 1.7 still disarmed (re-arm missed)
2026-10-03 v17v19 21:00-23:00 21:03 64% 38% 2.64 4.4 51.10 499 7.0 re-armed with the v17 profile
2026-10-04 v17v19 21:00-23:00 21:03 84% 63% 2.17 2.2 52.17 410 4.3

Outages and reliability

Every grid outage, with how the battery carried it and how much of the reserve that night's arbitrage had already used. This is the record for judging what the deeper discharge costs in backup.

MeasureValue
Outages6 (10.4 h)
Outages where the site went dark0
Outages that started after an arbitrage night, before the recharge0
Of those, site went dark0
DateStartEndDurationSoC at startLowest SoCLowest pack (V)Battery supplied (kWh)Site darkArbitrage use before (kWh)Notes
2026-10-0110:4514:123h2793%60%52.163.4no
2026-10-0120:2020:420h2256%52%51.920.5no
2026-10-0315:1016:491h3990%66%52.102.5no
2026-10-0416:3516:520h1790%87%52.600.3no
2026-10-0506:4009:272h4796%68%52.073.0no
2026-10-0510:351h5566%50%51.711.6nostill ongoing

Where to tweak

  • Unused battery headroom: the battery ends the window with an average 1.40 kWh above the 45% disarm floor (266190 UGX a night if shifted too). A longer or earlier window could use it.
  • Peak energy still bought from the grid: 5.86.2 kWh a night between 18:00 and midnight falls outside the window. That is the ceiling for more shifting, limited by battery size and the backup reserve.
  • Voltage margin: the lowest pack voltage so far is 50.94 V against the 50.4 V disarm trigger and 48.8 V inverter cut-off.
  • Spread: each shifted kWh earns about 189 UGX net (666.5 peak minus 429.7 off-peak at 90% round trip). A new quarterly tariff changes this directly.

Method

  • Shifted energy: battery discharge (ess0/ActivePower > 0) integrated over the configured window, with 10 minutes added at the end for the inverter clock lag. It counts only when the grid is present, because discharge during an outage is backup, not arbitrage.
  • Saving: shifted kWh at the peak rate, minus the off-peak cost of putting that energy back at 90% round-trip efficiency. It is energy only (no service charge, VAT or battery wear).
  • Recharge: battery charging between 00:00 and 06:00. It includes refilling any evening outage use, so it can exceed the shifted energy.
  • Config history: ADR-016 in the microgrid-gateway repo (v12 22:00-23:59, v13 off, v14 21:30-23:30 from 28 Sep, v17 21:00-23:00 from 30 Sep, v18 off 1-2 Oct, v19 re-armed from 3 Oct).
  • Outage: a minute counts as an outage when any phase of the inverter's grid-side meter (meter0) reads under 150 V or the inverter reports machine state 3 (off grid). Minutes with no data during an outage mean the edge lost power, which means the site went dark; an outage counts as dark at 5 such minutes or when SoC fell to 10% (the inverter's cut-off point seen on 24 Sep).
  • Arbitrage use before an outage: the energy that night's window took from the battery (grid present), for outages that start after the window and before 06:00. It is the backup the site did not have because of arbitrage. An outage that starts inside the window is marked, because from then on the discharge is backup.