Arbitrage Window and Thresholds (decision record)
This page records how the nightly TOU arbitrage window and battery thresholds at Sezibwa (gw-pi2) were chosen and changed. For the running night-by-night results see the Arbitrage Tracker. The engineering record is ADR-016 in the microgrid-gateway repository.
Current settings (from 30 Sep 2026)
| Setting | Value |
|---|---|
| Discharge window | 21:00 to 23:00 (config v17, microgrid-gateway PR #77) |
| Start threshold | 75% battery at window start, otherwise skip the night |
| Floor | 45%, stop discharging when reached |
| Recharge | from the grid at the off-peak rate from 00:00 (unchanged) |
How the thresholds are enforced. Until now, the 75% start rule and the 45% floor were enforced by hand, by deploying a "disarm" config and later a "re-arm" config. That meant a change and a deploy after every outage day. It stops now:
- The edge software will enforce both rules itself: skip the night if the battery is low at 21:00, stop at 45%, and resume the next night automatically. The work is tracked in microgrid-gateway issue #78.
- Until that is live, the window stays armed every night and nobody switches it off by hand. The inverter's own protections still apply (it switches the load to the grid at 10% when the grid is present, and cuts the load at 48.8 V).
Why 21:00 to 23:00
Site load inside each candidate window, over 75 to 77 nights (1 Jul to 28 Sep 2026). Battery use is corrected for the two real nights, which used about 20% less charge than the load alone predicts.
| Window | Average load | Heavy night (1 in 10) | Ends at, from a typical 86% start | Heavy nights ending below 45% | Ends at, from a 75% start |
|---|---|---|---|---|---|
| 21:30 to 23:30 (previous) | 3.5 kWh | 4.5 kWh | 59% | 0% | 48% |
| 21:00 to 23:00 (chosen) | 3.8 kWh | 4.8 kWh | 57% | 4% | 46% |
| 21:00 to 23:30 | 4.4 kWh | 5.3 kWh | 53% | 9% | 42% |
| 22:00 to 23:59 | 2.9 kWh | 4.0 kWh | about 64% | 0% | about 53% |
21:00 to 23:00 shifts slightly more energy than the previous window and stays clear of the floor on normal nights. 21:00 to 23:30 adds little energy, and from a 75% start it would end below the floor on most nights.
Typical start level. On normal evenings the battery is at about 86% at 21:00. It is lower only after a daytime outage (27 and 29 Sep started at 65% and 61%).
Outage timing. Of 14 outages seen from 25 Aug to 30 Sep (grid absent at least 30 minutes), 2 started between 21:00 and 06:00. The battery is refilled by about 01:30 after each night's discharge.
Value
Each kWh shifted from the peak rate (666.5 UGX) to the off-peak rate (429.7 UGX, at 90% round trip) saves about 189 UGX. Across the options above, arbitrage is worth roughly 15,000 to 20,000 UGX a month. The larger saving is solar (see "Solar Sizing Re-run, Sept 2026").
History
| Date | Config | Change |
|---|---|---|
| 26 Sep | v12 | First armed night, 22:00 to 23:59 |
| 27 Sep | v13 | Off after the overload outage (battery 65%) |
| 28 Sep | v14 | Window 21:30 to 23:30 |
| 29 Sep | v15 | Off after the morning outage (battery 61%) |
| 30 Sep | v16 | Re-armed 21:30 to 23:30 |
| 30 Sep | v17 | Window 21:00 to 23:00, start 75%, no more manual switch-offs |
Grid counts as absent during a phase collapse (22 Oct 2026)
Arbitrage is battery cycling with the grid usable; discharge while the grid is not usable is outage backup. On 21 Oct at Sezibwa, L2 and L3 fell to about 107 V while L1 stayed normal. The inverter rejects a supply with any phase below 170 V and ran the site on the battery, but the daily brief only looked at L1 and counted that discharge as arbitrage.
- The daily brief now treats the grid as off whenever any phase is below 170 V.
- The monitor (logger PR #94, ADR-018) treats the grid as absent during a total outage and while any phase is confirmed collapsed (below 180 V).
- Corrected 21 Oct: arbitrage gain UGX 579 from 3.14 kWh (first published as 914 from 4.91), backup 3.18 kWh.
Note, 26 Oct 2026: solar is live, night charge under review
Solar (4.8 kWp, inverter PV1) was connected on 26 Oct. With no export, the 00:00–06:00 grid charge fills the battery before sunrise and wastes midday surplus (~9.6 kWh/day). The evening window and the 15% floor stay as recorded here; the night grid-charge setting is under review with Aaron (stop, or cap ~50%) once PV output is proven. See Sezibwa Solar + Battery Operating Plan.